Fanuc

Troubleshooting Fanuc Servo Devices

Troubleshooting Fanuc Servo Devices

Recently we had a customer that we helped with troubleshooting a FANUC servo A20B-1003-0090 board that he was installing into an A06B-6058-H005 drive. A handful FANUC troubleshooting options are listed below.

Troubleshooting for the DCAI alarm:

[check items]

  1. Setting S2 for the S series
  2. Machine load
  3. Check connection of separate discharge unit

[Adjustment procedure]

A. Check amplifier setting S2. If the setting is incorrect, go to Cause 1. If the setting is correct, go to A-0.

A-0: Check whether a separate discharge unit is being used. If it is being used, go to A-1. If not being used, go to A-2.

A-1: Check the connection of the separate discharge unit. If the connection is incorrect, go to Cause 2. If connection is correct, go to A-2.

A-2: Check the acceleration/deceleration frequency. If the frequency is too high, go to Cause 3. If the frequency is low enough, go to A-3.

A-3: Replace the servo amplifier. If a DCAL alarm no longer occurs, go to Cause 4. If a DCAL alarm still occurs, go to Cause 3.

[Causes]

1). If the setting S2 of the S series servo amplifier is incorrect, a DC alarm is caused.

2). If the separate discharge unit is connected incorrectly, a DC alarm occurs.

3). Compared to the regenerative power of the amplifier, the regenerative energy of the motor is too large. (The inertia is too large or the acceleration/deceleration frequency is too high.) In this case, try to decrease the acceleration/deceleration frequency or install a separate discharge unit.

4). The discharge transistor (Q1) in the servo amplifier is defective.

MRO Electric and Supply has new and refurbished FANUC CNC products available, including FANUC Servo parts. We also offer repair pricing. For more information, please call 800-691-8511 or email sales@mroelectric.com.

Joe Kaminski

Joe Kaminski is an industrial automation specialist at MRO Electric. He has a background in industrial engineering and supply chain management. Joe has worked in the automation industry for over 10 years providing support to some of the largest companies in the world. For more info, visit www.mroelectric.com.

Share
Published by
Joe Kaminski

Recent Posts

End of Year Maintenance

End of Year Maintenance As the year comes to a close, it’s the perfect time…

2 days ago

Beginner’s Guide to Programming an Allen-Bradley PLC

Allen-Bradley Programmable Logic Controllers (or PLC) remain widely used in industrial automation. Programming their PLCs…

2 weeks ago

The Most Popular U.S. College Mascots

The game is almost over, and your team is losing. You can feel the crowd’s…

2 weeks ago

Every State’s Favorite OREO

Whether you’re loyal to the classic, double stuf, or thin OREOs, the addicting cookies always…

3 weeks ago

Legal and Safety Requirements Regarding Arc Flashes

Arc flash incidents are among the most dangerous hazards in the electrical industry, posing serious…

1 month ago

Understanding an Arc Flash

Understanding an Arc Flash An arc flash stand as one of the most dangerous electrical…

2 months ago