Siemens

MicroMaster 440 Parameter List and Fault Codes

Optimize the functionality of your Siemens Micromaster 440 by checking out our parameter list and guide to understanding Micromaster 440 fault codes and alarms.

MRO Electric has new and refurbished Micromaster 440 Drives in stock. Take a look at all of our Siemens products including motors, drives, HMIs, and much more. Be sure to check out our list of Siemens Micromaster 420 fault codes as well.  

If you need assistance with your Micromaster 440, our team can also repair non-functioning drives. To request a quote, please email sales@mroelectric.com or call 800-691-8511.

Micromaster 440 Parameter List

Following parameters are needed for quick commissioning of a Micromaster 440 drive.
NoNameAccess levelCstat
P0100 Europe / North America1C
P0205Inverter application3C
P0300Select motor type2C
P0304Motor voltage rating1C
P0305Motor current rating1C
P0307 Motor power rating1C
P0308Motor cosPhi rating2C
P0309 Motor efficiency rating2C
P0310Motor frequency rating1C
P0311Motor speed rating1C
P0320 Motor magnetizing current3CT
P0335Motor cooling2CT
P0640 Motor overload factor [%]2CUT
P0700Selection of command source1CT
P1000Selection of frequency setpoint1CT
P1080Min. speed1CUT
P1082Max. speed1CT
P1120Ramp-up time1CUT
P1120Ramp-down time1CUT
P1135 OFF3 ramp-down time2CUT
P1300Control mode2CT
P1500 Selection of torque setpoint2CT
P1910Select motor data identification2CT
P3900 End of quick commissioning1C

Micromaster 440 Faults and Alarms

In the event of a failure, the inverter switches off and one of the following fault codes appear on the display.
FaultPossible CausesDiagnose & RemedyQuit
F0001
OverCurrent
- Motor power (P0307) does not correspond to the inverter power (r0206)
- Motor lead short circuit
- Earth faults
Check the following:
1. Motor power (P0307) must correspond to inverter power (r0206).
2. Cable length limits must not be exceeded.
3. Motor cable and motor must have no shortcircuits or earth faults
4. Motor parameters must match the motor in use
5. Value of stator resistance (P0350) must be correct
6. Motor must not be obstructed or overloaded
- Increase the ramp time
- Reduce the boost level
OFF2
F0002
OverVoltage
- DC-link voltage (r0026) exceeds trip level (P2172)
- Overvoltage can be caused either by too high main supply voltage or if motor is in regenerative mode. Regenerative mode can be cause by fast ramp downs or if the motor is driven from an active load.
Check the following:
1. Supply voltage (P0210) must lie within limits indicated on rating plate .
2. DC-link voltage controller must be enabled (P1240) and parameterized properly.
3. Ramp-down time (P1121) must match inertia of load.
4. Required braking power must lie within specified limits.
NOTE:
Higher inertia requires longer ramp times; otherwise, apply braking resistor.
OFF2
F0003
UnderVoltage
- Main supply failed.
- Shock load outside specified limits.
Check the following:
1. Supply voltage (P0210) must lie within limits indicated on rating plate.
2. Supply must not be susceptible to temporary failures or voltage reductions.
OFF2
F0004
Inverter Over
Temperature
- Inverter overloaded.
- Duty cycle too demanding.
- Motor power (P0307) exceeds inverter power capability (r0206).
Check the following:
1. Load duty cycle must lie within specified limits.
2. Motor power (P0307) must match inverter power (r0206)
OFF2
F0011
Motor Over
Temperature
- Motor overloaded Check the following:
1. Load duty cycle must be correct
2. Motor nominal overtemperatures (P0626-P0628) must be correct
3. Motor temperature warning level (P0604) must match
OFF1
F0012
Inverter temp.
signal lost
Wire breakage of inverter temperature (heatsink) sensorOFF2
F0015
Motor temperature
signal lost
Open or short circuit of motor temperature sensor. If signal loss is detected, temperature monitoring switches over to monitoring with the motor thermal model.OFF2
F0020
Mains Phase
Missing
Fault occurs if one of the three input phases are missed and the pulses are enabled and drive is loadedCheck the input wiring of the mains phasesOFF2
F0021
Earth fault
Fault occurs if the sum of the phase currents is higher than 5 % of the nominal inverter current.
NOTE - Framesizes D to F
This fault only occurs on inverters that have 3 current sensors.
OFF2
F0022
Powerstack fault
That hardware fault (P0947 = 22 and
P0949 = 1) caused by the following events:
(1) DC-link overcurrent = short circuit of IGBT
(2) Short circuit of chopper
(3) Earth fault
(4) I/O board is not poperly inserted.
- Framesizes A to C (1),(2),(3),(4)
- Framesizes D to E (1),(2),(4)
- FramesizeF(2),(4)
- Since all these faults are assigned to one signal on the power stack, it is not possible to establish which one actually occurred.
- UCE failure was detected, when P0947 = 22 and fault value P0949 =12 or 13 or 14, depending on UCE (for MegaMaster only)
Check the I/O board. It has to be fully pressed home. OFF2
F0023
Output fault
One phase of output is disconnectedOFF2
F0024
Rectifier Over
Temperature
- Ventilation inadequate
- Fan inoperative
- Ambient temperature is too high.
Check the following:
- Fan must turn when inverter is running
- Pulse frequency must be set to default value
- Ambient temperature could be higher than
specified for the inverter
OFF2
F0030
Fan has failed
Fan no longer working- Fault cannot be masked while options module
(AOP or BOP) is connected.
- Need a new fan.
OFF2
F0035
Auto restart after n
Auto restart fault after n-restart tryOFF2
F0040
Automatic
Calibration Failure
MICROMASTER 440 onlyOFF2
F0041
Motor Data
Identification
Failure
Motor data identification failed.
- Alarm value =0: Load missing
- Alarm value =1: Current limit level reached during identification.
- Alarm value =2: Identified stator resistance less than 0.1% or greater than 100%.
- Alarm value =3: Identified rotor resistance less than 0.1% or greater than 100%.
- Alarm value =4: Identified stator reactance less than 50% and greater than 500%
- Alarm value =5: Identified main reactance less than 50% and greater than 500%
- Alarm value =6: Identified rotor time constant less than 10ms or greater than 5s
- Alarm value =7: Identified total leakage reactance less than 5% and greater than 50%
- Alarm value =8: Identified stator leakage reactance less than 25% and greater than 250%
- Alarm value =9: Identified rotor leakage inductance less than 25% and greater than 250%
- Alarm value = 20: Identified IGBT onvoltage less than 0.5 or greater than 10V
- Alarm value = 30: Current controller at voltage limit
- Alarm value = 40: Inconsistence of identified data set, at least one
identification failed Percentage values based on the impedance Zb = Vmot,nom / sqrt(3) / Imot,nom
0: Check that the motor is connected to the inverter.
1-40: Check if motor data in P304-311 are correct. Check what type of motor wiring is required (star, delta).
OFF2
F0042
Speed Control
Optimisation Failure
- Motor data identification failed.
- Alarm value =0: Time out waiting for stable speed
- Alarm value =1: Inconsistent readings
OFF2
F0051
Parameter EEPROM
Fault
- Read or write failure while saving nonvolatile
parameter.
- Factory Reset and new parameterization
- Change drive
OFF2
F0052
power stack Fault
- Read failure for power stack information or invalid data- Change driveOFF2
F0053
IO Eeprom Fault
- Read failure for IO EEPROM information or invalid data.- Check data
- Change IO module
OFF2
F0054
Wrong IO Board
1. Wrong IO board is connected.
2. No ID detected on IO board, No data.
- Check data
- Change IO module
OFF2
F0060
Asic Timeout
- Internal communications failure- If fault persists, change inverterOFF2
F0070
CB setpoint fault
- No setpoint values from CB (communication board) during telegram off time- Check CB and communication partnerOFF2
F0071
USS (BOP-link)
setpoint fault
- No setpoint values from USS during telegram off time- Check USS masterOFF2
F0072
USS (COMM link)
setpoint fault
- No setpoint values from USS during telegram off time- Check USS masterOFF2
F0080
ADC lost input
signal
- Broken wire
- Signal out of limits
OFF2
F0085
External Fault
- External fault triggered via terminal inputs- Disable terminal input for fault trigger.OFF2
F0090
Encoder feedback
loss
- Signal from Encoder lost1. Check encoder fitted. If encoder not fitted, set P400 = 0 and select SLVC mode (P1300 = 20 or 22)
2. Check connections between encoder and inverter
3. Check encoder not faulty (select P1300 = 0, run at fixed speed, check encoder feedback signal in P66)
Increase encoder loss threshold in P492
OFF2
F0101
Stack Overflow
- Software error or processor failure- Run self test routinesOFF2
F0221
PID Feedback below
min. value
- PID Feedback below min. value P2268- Change value of P2268.Adjust feedback gain.
F0222
PID Feedback above
max. value
- PID feedback above max. value P2267.- Change value of P2267.Adjust feedback gain.
F0450
BIST Tests Failure
Fault value:
1. Some power section tests have failed
2. Some control board tests have failed
4. Some functional tests have failed
8. Some IO module tests have failed. (MM 420 only)
16. Internal RAM failed on power-up check
- Drive may run but some features will not work properly.
- Replace drive.
F0452
Belt Failure
Detected
- Load conditions on motor indicate belt
failure or mechanical fault.
Check the following:
1. No breakage, seizure or obstruction of drive train.
1. If using an external speed sensor, check for correct function.Check parameters:
- P0409 (pulse per min at rated speed).
- P2191 (Belt failure speed tolerance).
- P2192 (delay time for permitted deviation)
2. If using the torque envelope, check parameters:
- P2182 (threshold frequency f1)
- P2183 (threshold frequency f2)
- P2184 (threshold frequency f3)
- P2185 (upper torque threshold 1)
- P2186 (lower torque threshold 1)
- P2187 (upper torque threshold 2)
- P2188 (lower torque threshold 2)
- P2189 (upper torque threshold 3
- P2190 (lower torque threshold 3)
- P2192 (delay time for permitted deviation)
4. Apply lubrication if required.

Need help with your Micromaster 440 drive?

Navigate through complex Micromaster 440 parameters and fault codes with ease. MRO Electric offers comprehensive support, from detailed parameter lists to expert repair services, ensuring your drive operates at peak performance.

Learn More About Our Siemens Repair Services
Joe Kaminski

Joe Kaminski is an industrial automation specialist at MRO Electric. He has a background in industrial engineering and supply chain management. Joe has worked in the automation industry for over 10 years providing support to some of the largest companies in the world. For more info, visit www.mroelectric.com.

Share
Published by
Joe Kaminski

Recent Posts

End of Year Maintenance

End of Year Maintenance As the year comes to a close, it’s the perfect time…

2 days ago

Beginner’s Guide to Programming an Allen-Bradley PLC

Allen-Bradley Programmable Logic Controllers (or PLC) remain widely used in industrial automation. Programming their PLCs…

2 weeks ago

The Most Popular U.S. College Mascots

The game is almost over, and your team is losing. You can feel the crowd’s…

2 weeks ago

Every State’s Favorite OREO

Whether you’re loyal to the classic, double stuf, or thin OREOs, the addicting cookies always…

3 weeks ago

Legal and Safety Requirements Regarding Arc Flashes

Arc flash incidents are among the most dangerous hazards in the electrical industry, posing serious…

1 month ago

Understanding an Arc Flash

Understanding an Arc Flash An arc flash stand as one of the most dangerous electrical…

2 months ago